ECONOMY – SAFETY – EFFICIENCY

iLEC MCT – Epoxy Casting Current Transformer

Epoxy Casting Current Transformer

Split-Core Model JP-812

Introduction

The JP Series split-core current transformers are specially designed to facilitate both new and retrofit installations in electrical systems. Featuring an easily opened split-core design, they can be installed without disconnecting cables or opening busbar circuits. Unlike conventional current transformers, which require the primary circuit to be interrupted during installation, the JP Series can be installed quickly and conveniently without interrupting the power supply, significantly reducing installation time and costs.

Features

  • Bus-bar mounting design.
  • Very easy to mount, especially installing Ct on existing bus-bar or cable system.
  • Wide inner window, allowing clamping of big cables or bus-bar.
  • Wide range of sizes to accommodate all the existing installations, wide range ratio for each size.
External Features

General Spcifications

Parameter Value
Rated Frequency 50/60Hz
Rated insulation voltage 3kV AC (1 min)
Rated short-time thermal current (Ith) 60In / 1s
Rated dynamic current (Idyn) 2.5Ith
Rated voltage (Un) 0.72kV AC
Continuous current (Id) 1.2In
Operating temperature -10ºC ~ 50ºC
Maximum temperature rise 50ºC
Housing self-extinguishing class Vo
Safety factor FS 5
Ratio 100/5A to 10000/5A or 20/1A to 3000/1A
Following Standards IEC 60044-1, IEC 61869-2
Environment Indoor

Ordering Code for JP Series

Ordering Code for JP Series

1. Ordering Information

Ordering Code Ratio Burden – Cl 1.0 Burden – Cl 0.5
JP-812-0500 500/5A 5.0VA 3.75VA
JP-812-0600 600/5A 5.0VA 3.75VA
JP-812-0800 800/5A 5.0VA 5.0VA
JP-812-1000 1000/5A 7.5VA 5.0VA
JP-812-1200 1200/5A 7.5VA 5.0VA
JP-812-1500 1500/5A 10VA 7.5VA
JP-812-1600 1600/5A 10VA 7.5VA
JP-812-2000 2000/5A 10VA 10VA
JP-812-2500 2500/5A 10VA 10VA
JP-812-3000 3000/5A 15VA 10VA
JP-812-3200 3200/5A 15VA 10VA
JP-812-4000 4000/5A 20VA 15VA

2. Dimension

Dimension JP-812
Model Width Height Thickness Window size
JP-812 151 229 60 82 x 122

3. Choosing Cable