ECONOMIC – SAFETY – EFFECTIVE

Fuse Link width Knife Contact

NH00 Series

General Description

Fuse bases and fuse links are essential components in low-voltage power distribution systems, designed to protect electrical circuits and equipment against overcurrent and short-circuit conditions. The fuse link interrupts the circuit in the event of a fault, while the fuse base provides secure installation, safe operation, and easy replacement. Together, they enhance system reliability and ensure stable and safe electrical operation.

  • iLEC NH00 fuse links are low-voltage square body fuses with knife contacts, designed to provide full-range protection for electrical systems.
  • The product features a sealed construction made of high-quality insulating materials with effective arc-quenching capability, ensuring reliable protection for cables, conductors, and electrical equipment against overload and short-circuit conditions.
  • iLEC NH00 fuse links are suitable for use in industrial switchboards and power distribution systems.
  • Typical applications include industrial switchboards, power distribution panels and electrical protection systems.
  • Compliant with international standards IEC 60269, VDE 0636 and CE.

Technical Parameter

Models NH00-50A / 63A / 80A / 100A / 125A / 160A
Standard IEC 60269, VDE 0636, CE
Dimensions/Mounting According to DIN VDE 43 620 and VDE 43 623
Operating classes gG, aM (short-circuit protection only)
Rated voltage AC 500V / 690V ~
Rated breaking capacity AC 500V – 120kA / AC 690V – 50kA
Mounting position Optional, preferable vertical
Operating temperature -30ºC to +50ºC
Relative Humidity At 95% RH, non-condensing
Apllications Cable protection, Motor protection

Dimension Drawing

Fuse Time-Current Characteristic

NH00 Series Fuse Links (50A to 160A)

Resources & Support