Aerosol Fire Extinguisher Module
Model AFE-10 / AFE-20 / AFE-30
General
iLEC AFE Series is a compact, high-efficiency aerosol fire extinguisher designed for rapid fire suppression in enclosed spaces. It automatically activates via thermal detection and releases aerosol fire-extinguishing agents within 15 seconds, providing total flooding protection for small volumes up to 0.1m³.
This device is ideal for applications in electrical cabinets, server rooms, and other confined areas where traditional fire suppression systems may be impractical. Notably, it operates without any electrical power supply, relying solely on thermal activation for independent functionality.
Their exterior design and dimensions are aligned with standard circuit protection products, ensuring a unified appearance and seamless side-by-side installation for consistent panel aesthetics and layout.
Features
- Rapid Response: Triggers within 15 seconds of reaching the set temperature (170ºC); discharge duration ≤ 6 seconds.
- Eco-Friendly: Non-toxic, non-corrosive, and ozone-friendly with no atmospheric depletion.
- Long Shelf Life: 10-year validity period with minimal maintenance.
- Easy Installation: Supports both 35mm DIN-rail mounting and 3M adhesive side-mount.
- Compact Design: At only 18mm wide, it fits tight enclosures and crowded control panels without compromising accessibility.
- Power-Independent: No electricity required; fully thermal-activated.
Technical Specifications
| Model name | AFE-10 | AFE-20 | AFE-30 |
| Agent dosage | 10g | 20g | 30g |
| Protected volume (typical, application-dependent) |
0.1m³ | 0.2m³ | 0.3m³ |
| Activation method | Thermal, no external power | ||
| Activation temperature | 170ºC | ||
| Activation response | Activated within 15s reaching temperature (initiates aerosole generation) |
||
| Aerosole generation duration | ≤ 6s | ||
| Mounting | 35mm DIN-rail or 3M adhesive side mount (Customized) | ||
| Housing color | Red (or Orange) | ||
| Thermal probes | 2 Probes (top and bottom) | ||
| Probe cable length | Standard: 10cm/probe – Customizable: 10-50cm/probe | ||
| Operating temperature | -50ºC to +90ºC | ||
| Humidity tolenrance | < 95% RH (non-condensing) | ||
| Service life | Up to 10years (storage / installation condition dependent) |
||
Technical Specifications
- Warnings: Do not tamper with the device or expose it to open flames during installation. Avoid inhalation of aerosol during discharge evacuate immediately.
- Precautions: Not suitable for spaces with explosive gases or where personnel are present without proper ventilation.
- Emergency Response: In case of accidental activation, wear protective gear and ensure area is safe before re-entry.
- Disposal: Dispose of expired units as hazardous waste per local environmental regulations.
- Important:This device is not a substitute for comprehensive fire safety systems. Always integrate with alarms and evacuation plan.
DIN rail mounting example
Resources & Support
- Technical document: [English] [Vietnamese]